AQ-102 Arc flash protection

AQ 102 is a sophisticated micro-processor based arc flash protection unit for arc light detection. It is designed to minimize the damage caused by an arcing fault (arc flash) by tripping the circuit breaker sourcing the fault current. The AQ 102 complete system self-supervision function provides the highest level of dependability by continuously monitoring all internal system functions along with external connections.


Ask for an offer
  • ARC
  • Light L>
  • Light and Pressure L>/P>
  • Circuit Breaker Failure Protection 50BF
  • Trip time using mechanical trip relays: 7 ms
  • Reset time (arc light stage): 2 ms
  • Protection operational after power up: 88 ms
  • Applicable sensors: max. 3 sensor loops
  • AQ 06 plastic fiber sensor (5-50m length)
  • AQ 07 glass fiber sensor (5-60m length)
  • Trip Relays T1, T2, T3, T4
  • Number: 3 NO + 1 NC or 4 NO
  • Rated voltage: 250V ac/dc
  • Continuous carry 5A
  • Make and carry for 0.5s: 30A
  • Make and carry for 3s: 16A
  • Breaking capacity DC, when time constant L/R=40ms: 40W; 0.36A at 110 Vdc
  • Contact material: AgNi 90/10
  • Binary Output BO1
  • Rated voltage: +24V dc
  • Rated current: 20mA (max)
  • Number of outputs: 1
  • Binary Iinputs BI1, BI2
  • Treshold Voltage voltage : 24 or 110 or 220Vdc
  • Rated Voltage: 250 V
  • Rated current: 3 mA
  • Number of inputs: 2
  • Power supply
  • Us: 80…265Vac/dc (option 18…72Vdc)
  • Maximum interruption: 100ms
  • Maximum power consumption: 5W
  • Standby current: 90mA
  • 12 Indication LED's
  • Autoconfiguration
  • Indication reset
  • System check
  • Sensors and wiring
  • Binary I/O
  • Trip coil
  • Power supply
  • Iternal voltages
  • Settings