AQ-101 Arc flash protection

AQ 101 is a sophisticated micro-processor based arc flash protection unit for arc light detection. It is designed to minimize the damage caused by an arcing fault (arc flash) by tripping the circuit breaker sourcing the fault current. The AQ 101 complete system self-supervision function provides the highest level of dependability by continuously monitoring all internal system functions along with external connections.

AQ 101 can be used as a stand-alone unit or as a part of a more complex arc protection system through the binary bus.

Features:

  • Wide range power supply (18-72Vdc or 80-265Vac/dc)
  • Max 12 arc light point sensors
  • Max 1 fiber loop sensor (option)
  • 4 trip relays (7ms trip time)
  • 1 system failure relay
  • 1 fast binary output
  • 2 fast binary inputs
  • 1 push button
  • Non-volatile memory
  • 12 indication LEDs


Ask for an offer
  • ARC
  • Light L>
  • Light and Pressure L>/P>
  • Circuit Breaker Failure Protection 50BF
  • Trip time using mechanical trip relays: 7 ms
  • Reset time (arc light stage): 2 ms
  • Protection operational after power up: 88 ms
  • Applicable sensors
  • AQ-01 light sensor (activation at 8/25/50 klx)
  • AQ 01M portable sensor kit
  • AQ-02 light and pressure sensor
  • AQ-06 plastic fiber sensor (5-50 m length) (option)
  • AQ-07 glass fiber sensor (5-60 m length) (option)
  • Trip Relays T1, T2, T3, T4
  • Number: 3 NO + 1 NC or 4 NO
  • Rated voltage: 250 Vac/dc
  • Continuous carry: 5 A
  • Make and carry for 0.5 s: 30 A
  • Make and carry for 3 s: 16 A
  • Breaking capacity DC, when time constant L/R = 40 ms: 40 W; 0.36 A at 110 Vdc
  • Contact material: AgNi 90/10
  • Binary Output
  • Rated voltage: +24 Vdc
  • Rated current: 20 mA (max)
  • Number of outputs: 1
  • Binary Iinputs BI1, BI2
  • Threshold voltage: 24 or 110 or 220 Vdc
  • Rated voltage: 250 Vac/dc
  • Rated current: 3 mA
  • Number of inputs: 2
  • Power supply
  • Us: 80…265 Vac/dc (option 18…72 Vdc)
  • Maximum interruption: 100 ms
  • Maximum power consumption: 5 W
  • Standby current: 90 mA
  • 12 Indication LED's
  • Multifunction push button
  • Autoconfiguration
  • Indication reset
  • System check
  • Sensors and wiring
  • Binary I/O
  • Trip coil
  • Power supply
  • Internal voltages
  • Settings
  • AQ-200 series
  • AQ-300 series
  • AQ-100 series
  • Link to AQ SAS manual